Figure 2. Filter/Separator Unit Post-Operation
FIELD PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)

Maintenance Manual For Filter/Separator, Liquid Fuel, 50-Gpm, 100-Gpm, & 350-Gpm Page Navigation
  17    18    19    20    21  22  23    24    25    26    27  
img
.
TM 5-4330-263-13&P
0006 00
NOTE
If filter/separator vessel is to remain installed in fueling system, open upstream valve and refer to "Operation Under
Usual Conditions" on page 0006 00-2 to fill vessel with fuel.
6.
If filter/separator vessel is to be removed and relocated, obtain a suitable container and place it below fuel drain
valve (4).
Diesel/jet fuel is toxic to skin, eyes and respiratory tract. Personnel must wear appropriate hand and eye
protection (nitrile gloves and goggles). Wash skin thoroughly with soap and water if exposed. Flush eyes
with clear water for at least 15 minutes in case of contact with diesel/jet fuel.
7.
Open fuel drain valve (4) and drain contents of vessel.
8.
When all fuel has drained, close fuel drain valve (4) and purge valve (1) and disconnect hoses from inlet and outlet
couplings.
9.
If installed, disconnect and stow detector kit.
10. Drain residual fuel from hoses.
11. Dispose of excess fuel in accordance with federal and local regulations.
END OF WORK PACKAGE
0006 00-5/(0006 00-6 blank)