TM 10-4330-236-13&P
3-3. TROUBLESHOOTING.
Refer to troubleshooting table 3-1.
NOTE
Be sure to read all warnings in the front of this manual before performing the troubleshooting
procedures.
Table 3-1. Operator Troubleshooting for 200 GPM Filter-Separator.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. Ice crystals in filter.
High DP gage (1) reading, if high (in the yellow zone on gage dial)
Step 1. Allow fuel to circulate while monitoring DP gage (1) reading.
Step 2. If DP reading does not go down to green. notify unit maintenance.
Step 3. Check position of defrost door (2). Adjust door for more heat. Refer to para 2-6.
Figure 3-1. Malfunction 1 Ice Crystals 3-2
3-2