TM 10-4330-230-12&P
2-10. Operating Procedures. (Figure 2-3)
a.
b.
c.
2-11
a.
b.
c.
Open outlet side valve (1) to full open position.
WARNING
Do not operate the filter/separator until the bonding cable on the fuel nozzle has been
attached to the vehicle. This bonding must be accomplished prior to opening the filler
cap.
Observe the water level sight gage (2). If level of water is above upper line, open the manual drain valve (3)
and drain water into suitable container until water level is at lower line.
Drain water daily or when ball in sight gage reaches the top mark on the sight gage.
Stopping Procedure. (Figure 2-4)
Stop the system pumping unit. Refer to the applicable pumping system technical manual.
Close the inlet valve (1).
Close the outlet valve (2).
l Do not drain fuel from the unit on the ground.
Drain fuel into a container that can be
closed otherwise fire hazard or environmental contamination could result
l Use protective equipment to prevent skin and eye contact with fuel.
NOTE
If the filter/separator is not to be in frequent use, drain the tank. Use following
instructions.
d. Open pressure vent valve (3) to repressurize unit.
e. Open manual drain valve (4) and drain contents of filter/separator (5) into suitable container.
2 -8