TM 10-4330-230-12&P
Section Ill. OPERATION UNDER USUAL CONDITIONS
Paragraph
Page
2-9
Starting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-10
Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2-11
Stopping Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2-9. Starting Procedure. (Figure 2-2)
WARNINGS
l Do not operate the filter/separator unit until it has been connected to a suitable ground.
A static discharge could ignite the fuel or cause an explosion of the fuel vapor.
l Do not smoke or use open flame in vicinity of filter /separator. Use protective
equipment to prevent skin and eye contact with fuel.
l Make sure fire extinguishers and fire fighting equipment are available in the immediate
area. Be extremely careful when using a fire extinguisher in an enclosed area.
Provide adequate ventilation.
a. Make sure water drain valve (1) is closed.
b. Ensure the inlet (2) and outlet (3) connections are tight.
c. Slightly open the pressure vent valve (4) to allow entrapped air to escape.
d. Start the system pumping unit. Refer to the applicable pumping system technical manual.
e. Open inlet valve (2) slightly to allow the filter/separator (5) to fill slowly with as little pressure as possible.
NOTE
When the unit is completely filled, fuel will come through the vent pressure valve.
f. Close pressure vent valve (4). Make a visual inspection of all connections, joints, and piping components
for leaks.
g. Fully open inlet valve (2).
2-6