2-10. PREPARATION FOR MOVEMENT - continued
b.
Isolate filter-separator by closing up-stream and down-stream valves. Refer to system operating manual.
For steps c through k refer to figure 2-21.
c.
Place container under air vent tube assembly (1) andopen air vent valve (2) to purge air. Refer to para 2-
6.
NOTE
For disposal of contaminated fuel, refer to FM 10-20.
d.
Place container under drain elbow (3) and turn drain valve handle (4) open to drain water from the sump.
Refer to para 2-6.
NOTE
For disposal of contaminated fuel, refer to FM 10-20.
e.
Pull locking arms (5) up and out from discharge hose coupling (6) and disconnect discharge hose
assembly (7) from adapter coupling (8).
f.
Install dust plug (9) in discharge hose coupling (6) and p
ush back against locking arms (5) to secure dust
plug in hose coupling.
g.
Pull locking arms (10) up and out from adapter coupling (11) and disconnect adapter assembly (12) from
filter-separator outlet coupling (13).
h.
Install dust plug (14) in adapter coupling (11) and push back against locking arms (10) to secure dust plug i
1 adapter coupling.
i.
Install dust cap (15) on adapter coupling (8) and push back against locking arms (I 6) to secure dust plug
cap adapter coupling.
j.
Install dust cap (17) on filter-separator outlet coupling (13) and push locking arms (18) back against dust
cap (17) to secure dust cap on outlet coupling.
WARNING
To avoid burns, wear hand protection when adjusting defrost door. The door and shroud may be
very hot.
k.
Place the defrost door (19) in the fourth notch (fully closed) of the adjustment plate (20).
2-39