TM 10-4330-236-13&P
2-5.
ASSEMBLY AND PREPARATION FOR USE - continued.'
WARNINGS
· Fuel is flammable and toxic. Avoid breathing of fuel vapors. Keep open flame and sparks away
from pump assemblies, fuel hoses and spilled fuel on the ground.
· To prevent injury to personnel and damage to the equipment, use care when connecting;
coupling to avoid getting debris on coupling mating surfaces. To prevent leaks and secure tight
connections, make sure gaskets are installed in all female quick disconnect couplings.
· To prevent injury to personnel and equipment, do not apply excessive pressure or force on the
locking arms when securing dust caps or dust plugs. Excessive pressure could break the locking
arms and cause leaks due to poor connections.
NOTE
Make certain that the quick disconnect cams on female coupling halves are pulled all the way so
that male coupling halves can be securely seated. Check to see that gaskets are installed in each
female coupling half.
e. Adapter Assembly. Water Detection. Installation
. (Refer to Figure 2-11)
(1)
Pull locking arms (1) up and out from dust cap (2) and remove dust cap (2) from filter-separator outlet
coupling (3).
(2)
Pull locking arms (4) up and out from coupling (5) and remove dust plug (6) from adapter assembly (7).
(3)
Make sure that the bevel (8) on the sampling probe(9) is pointed in the direction of female coupling (5).
(4)
Attach adapter assembly (7) onto outlet coupling (3). Push locking arms (4) back against coupling (5) to
secure adapter assembly (7) to filter-separator outlet coupling (3).
(5)
Install dust plug (6) into dust cap (2) and push locking arms (1) back against dust cap (2) to secure dust
plug (6).
2-23